Vulnerability Assessment of Selected Buildings
Designated as Shelters
St Kitts - Nevis

Organization of American States
General Secretariat
Unit for Sustainable Development and Environment

OAS Caribbean Disaster Mitigation Project
OAS-ECHO Project to Reduce the Vulnerability of School Buildings to Natural Disasters
1998


This report was prepared by
Tony Gibbs of Consulting Engineers Partnership Ltd.

TABLE OF CONTENTS

1 INTRODUCTION

1.1 The Purpose of the Project
1.2 Terms of Reference
1.3 Natural Hazards in the Caribbean
1.3.1 Earthquakes
1.3.2 Volcanic Activity
1.3.3 Tsunamis
1.3.4 Hurricanes
1.3.5 Torrential Rains
1.3.6 Storm Surge
1.3.7 Landslides

2 INVESTIGATION PROCEDURE

2.1 Briefing
2.2 Field Surveys
2.3 Field Reviews
2.4 Desk Studies

3 RESULTS

3.1 Vulnerability to Hurricanes
3.1.1 General Observations
3.1.2 Aspects of Vulnerability
3.1.3 Summary of Results
3.2 Vulnerability to Torrential Rain
3.2.1 General Observations
3.2.2 Summary of Results
3.3 Vulnerability to Earthquakes
3.3.1 Multi-hazard Design
3.3.2 Differences Between Designing Against Earthquakes and Hurricanes
3.3.3 Aspects of Vulnerability
3.3.4 Summary of Results

4 GENERAL ISSUES

4.1 Impact of Hurricanes on Caribbean Schools
4.2 Hazards versus Disasters
4.3 Codes and Standards
4.4 The Regulatory Environment
4.5 Public Awareness
4.6 Vulnerability Surveys
4.6.1 Qualitative Assessment
4.6.2 Analytical Evaluation
4.7 Disaster Mitigation after the Event
4.8 Maintenance as a Tool for Mitigation

5 HURRICANES LUIS AND MARILYN IN ST KITTS

5.1 Damage and Repairs
5.2 Recommendations
5.3 Classes of Vulnerability
5.4 Further Work

Appendix I Survey Forms

  • Hurricane Vulnerability Assessment
  • Seismic Vulnerability Assessment - Part I
  • Seismic Vulnerability Assessment - Part II
  • Appendix II Technical Paper (only introduction available in web format)

    Hassan, Ahmed F. and Sozen, Mete A., Seismic Vulnerability Assessment of Low-Rise Buildings in Regions with Infrequent Earthquakes, ACI Structural Journal, January - February 1997

    Appendix III    Photographs of Selected Buildings in St Kitts - Nevis


    1 INTRODUCTION

    1.1 The Purpose of the Project

    Throughout the world, including the Caribbean, natural hazards cause as much damage to educational facilities as they do to buildings of less importance. This is both regrettable and avoidable. Educational facilities deserve special attention because of their roles during the active periods of storms and also as post-disaster assets.

    It is traditional for schools to be used as hurricane shelters. It goes without saying, therefore, that the damage and destruction of schools would put the sheltered population at risk during severe storms. Also, damage and destruction of such schools would not facilitate the use of school buildings for temporary housing after hurricanes. The longer-term problem of loss of educational facilities is arguably even more severe. If the children are not at school the parents' work is often adversely affected (in part because of "baby-sitting" problems). There is also the inevitable disruption of the pupils' education.

    It is often said that safe buildings may not be affordable, especially in relatively poor developing countries. This is a fallacy. Particularly with respect to hurricane resistance, safe buildings are not only technically feasible but also achievable at very modest cost. This thesis has been tested and confirmed on several occasions over the years.

    The Caribbean Development Bank (CDB) proposes to assist its borrowing members in reducing the vulnerability of designated shelters to natural hazards. The initial screening of these designated properties is being carried out in some of the CDB member countries through the auspices of the Organisation of American States (OAS) using CDMP [1] and ECHO [2] funding.

    It is recognised that the suitability of properties for use as emergency shelters depends on several factors other than structural safety. Some of these factors are location, size, water storage and supply, sanitary facilities, kitchen facilities, standby power and telecommunications within the facility and externally. Most of these issues are already being addressed by other agencies. The focus of this study is on the physical vulnerability of the built facilities to wind forces, torrential rain and seismic forces. This initial screening will provide the relevant local agencies with some of the input required for selection of properties for the follow-on, CDB-funded projects.

    1.2 Terms of Reference

    The portions of the overall Terms of Reference (ToR) relevant to the subject of the present report are:

    As articulated above, an important objective of this project is technology transfer and the broadening of the pool of "disaster mitigation" engineers in the region. Therefore, the active involvement of local engineers (assumed to be from the relevant public works departments) was essential.

    1.3 Natural Hazards in the Caribbean

    The primary natural hazards facing the islands of the Caribbean are earthquakes and hurricanes. Some of the islands are also subjected to instances of volcanic activity. There are also the related hazards of tsunamis and storm surge.

    Torrential rains can also, by themselves, be considered natural hazards since they often occur without the concurrent occurrence of hurricanes and sometimes result in disastrous flooding of low-lying areas. Likewise, some landslides are naturally occurring, isolated events.

    1.3.1 Earthquakes

    All of the Commonwealth Caribbean countries, with the exceptions of Bahamas and Guyana, lie close to the known tectonic plate boundaries. The North American Plate is moving westward with respect to the adjacent Caribbean and South American Plates at a rate of approximately 2 centimetres per year. A moderate level of inter-plate activity is generated along these boundaries. Along the northern margin, including areas in the vicinities of Jamaica and the Virgin Islands, moderate earthquakes of shallow depth are generated. Near the plate boundaries there are also intra-plate earthquakes. In the northern Caribbean these intra-plate earthquakes are caused by internal deformation in a slab of the North American Plate. Concentrations of these earthquakes occur at depths of up to 200 kilometres.

    Seismic events in the Eastern Caribbean are principally associated with a subduction zone at the junction of the Caribbean Plate and the North American Plate. The North American Plate dips from east to west beneath the Caribbean Plate along a north-south line just east of the main island arc. This leads to a moderate level of inter-plate seismicity. Superimposed on this is a pattern of intra-plate activity. There is a concentration of such activity in the Leeward Islands where the subduction of the Barracuda Rise imposes additional stresses on both the "subducted" North American Plate and the overriding Caribbean Plate. The earthquakes there are generally shallow. In the region north-west of Trinidad there is another concentration of earthquake activity where the strike of the plate boundary changes direction. These earthquakes are of intermediate depth.

    Over the past forty-five years a considerable amount of research has been carried out on the seismicity of the Caribbean by the Seismic Research Unit (SRU) of the University of the West Indies (UWI). The engineering community has been requesting more and more assistance from the SRU in interpreting the fundamental research and developing "code" values for seismic forces for use in structural design. The most recent published work in this field is that of SRU's former head, Dr John Shepherd, now at Lancaster University (England).

    The Pan-American Institute of Geography and History (PAIGH) is based in Mexico City. The Geophysical Commission of PAIGH is the executing agency for a major project (funded by IDRC [4] ) for preparing Seismic Hazard Maps for Latin America and the Caribbean and headed by Dr J G Tanner. Dr John B Shepherd participated in this project as the Caribbean specialist.

    The final report and mapping from this project indicate that St Kitts and Nevis lie between the iso-acceleration lines representing 300 gals [5]   and 450 gals. These are peak ground accelerations with a probability of non-exceedance of 90% in 50 years. The Caribbean Uniform Building Code (CUBiC), which is incorporated in the draft St Kitts - Nevis Building Code [6], assigns a zone factor (Z) of 0.75 to St Kitts and Nevis. Both of these references indicate a serious earthquake hazard for St Kitts - Nevis.

    1.3.2 Volcanic Activity

    Several of the islands of the Eastern Caribbean are volcanic in origin. The volcanoes there are considered to be either active or dormant. Both St Kitts and Nevis exhibit volcanic activity. This, however, is outside the scope of this report.

    1.3.3 Tsunamis

    A tsunami (or seismic sea wave or tidal wave) is a series of ocean waves generated by any large-scale, short-duration disturbance of the free surface of the ocean. The majority are related to tectonic displacements associated with earthquakes at plate boundaries. However, erupting volcanoes, landslides or underwater explosions can also generate tsunamis. In the open ocean, tsunamis may have wavelengths of up to several hundred miles but heights of less than 1 meter. Because this ratio is so large, tsunamis can go undetected until they approach shallow waters along a coast. Their height as they crash upon the shore mostly depends on the geometry of the submarine topography offshore, but they can be as high as 30 meters.

    A tsunami travels at an average velocity of 500 to 600 kilometres per hour rising to a maximum of 800 km/h. Therefore within one hour of a major occurrence at Kick 'em Jenny (just north of Grenada), many of the islands of the Eastern Caribbean (including St Kitts and Nevis) will be affected. This, however, is outside the scope of this report.

    1.3.4 Hurricanes

    Much is not known about the storms which occurred in the Caribbean in the years before the advent of Columbus. But, of course, the European did not bring hurricanes to the

    Caribbean. Indeed the very name is derived from the Mayan storm god Hunraken and the Arawak word hurican, which meant the devil wind. The greatest of all recorded hurricanes occurred from 10th to 18th October 1780. Nearly 20,000 people perished as the storm hit virtually every island from Tobago in the south-east through the Windward and Leeward Islands and across to Hispaniola and Cuba. In the last 60 years in the Caribbean another 20,000 people have lost their lives because of hurricanes.

    The Caribbean lies in the North Atlantic Ocean, one of the six main tropical areas of the earth where hurricanes may develop every year. Within the 111 years between 1886 and 1996, approximately 1000 tropical storms have been recorded in the North Atlantic. About half of these attained hurricane strength.

    The destructive potential of a hurricane is significant due to high wind speeds and torrential rains that produce flooding and occasional storm surges with heights of several feet above normal sea level.

    The pattern in recent times has been a reduction of deaths and injuries (because of better warning systems and other preparedness activities) and an increase in property damage (because of commercially-driven unsuitable building practices and locations).

    The Caribbean Uniform Building Code (CUBiC), which is incorporated in the draft St Kitts - Nevis Building Code, assigns a reference pressure of 0.83 kPa [7] to St Kitts and Nevis. This is equivalent to a 10-minute sustained wind speed of 37.2 m/s [8] (83 mph) or an equivalent 3-second gust speed of 56 m/s (125 mph). These figures relate to a 50-year return period.

    1.3.5 Torrential Rains

    Although heavy rains often accompany hurricanes, severe rainfall events resulting in flooding are also, and frequently, associated with troughs and tropical depressions. The risk of flooding is therefore not restricted to, nor more likely to occur, during hurricane events.

    Drainage systems and structures in the Caribbean are generally designed for rainfall events having return periods of 20 years. This means that such systems are likely to become overloaded and cause some degree of flooding when rainstorms are experienced with return periods greater than 20 years. No guidance on this is provided in CUBiC. However, consideration should be given to moving this common standard to a longer return period. Intensity-duration-frequency relationships for rainfall events are required for rational engineering analysis. These are available from the Caribbean Meteorological Institute.

    The damage caused by flooding depends on the type and elevation of facilities in the location. The results of flooding may range from the inconvenience of temporarily

    submerged driveways to the loss of equipment and finishes inside flooded buildings and consequential disruption of the functions.

    Flooding has been the cause of many of the deaths and of much property damage as well. Clearly, location is critical when it comes to flood risk. Low-lying lands, riverbanks and lands adjacent to gullies are to be avoided if possible. If not, deliberate drainage measures must be taken. Usually this is a municipal responsibility, at least in terms of overall control, since what happens to one property can easily be affected by a neighbour's actions.

    The design of external works for shelter premises would include consideration of local flooding. It would not be practical to study the overall catchment area for the design of each particular site. However, some general appraisal of the adjacent areas should be carried out as input for the design of on-site drainage structures.

    1.3.6 Storm Surge

    Storm surge is associated with hurricanes and consists of unusual volumes of water flowing onto shorelines. Storm surge has been responsible for much of the damage caused by hurricanes, especially in large, low-lying coastal settlements.

    Storm surge is a complex phenomenon which behaves quite differently from one shoreline to another. The several main components governing their behaviour are:

    Astronomical Tide:

    water levels due to tidal variation;

    Initial Water Level:

    elevated basin-wide water levels caused by larger storms;

    Pressure Deficit:

    elevated water levels caused by low pressure systems;

    Inland Runoff:

    raised water levels in rivers and sea outfalls due to prolonged rainfall;

    Current Surge:

    ocean currents caused by high winds leading to the "piling up" of shallow waters;

    Wave Setup:

    water accumulating from continuous trains of waves on breaking on the shoreline; and

    Wave Action & Runup:

    effect of actual waves superimposed on the above factors.

    The increase in coastal settlement has put much of our economic investment at risk from sea damage. Future rises in sea level can only make this condition more acute. Storm surge caused by hurricanes causes the most dramatic damage. Waves cause damage without accompanying surge but they are also superimposed on storm surge.

    As well as causing flooding and damage to coastal structures, storm surge may also precipitate flooding further inland through the blockage of the outfalls of drainage systems. This is outside of the scope of the present exercise.

    1.3.7 Landslides

    Most landslides in Caribbean islands cannot be regarded as natural hazards since they are brought about by inappropriate farming practices although triggered by natural events. Another man-induced class of landslides is road construction in mountainous areas. Often the cut embankments are too steep for stability. Often the down-slope fills are unstable.

    There are, however, a few situations where nature itself produces the events. This phenomenon is outside the scope of this report.


    2 INVESTIGATION PROCEDURE

    2.1 Briefing

    On 10 November 1997 an initial briefing took place at the office of Bentley Associates in Basseterre, St Kitts. Those present were:

    Michael Bentley

    Director (Crisis Management)

    National Emergency Management Agency

    Carl A Herbert

    Administrative Officer

    National Emergency Management Agency

    R A Peter Jenkins

    Director (Assessment)

    National Emergency Management Agency

    Cromwell Williams

    Engineer

    Public Works Department

    David L Folkes

    Engineer

    Consulting Engineers Partnership Ltd

    Tony Gibbs

    Director & Consultant

    Consulting Engineers Partnership Ltd

    The overall programme was explained and Consulting Engineers Partnership Ltd (CEP) delivered the survey forms to Eng Williams.

    On 11 November Engs Williams and Gibbs met to review the forms. During this meeting certain changes to the forms were agreed and revised forms were sent electronically to Eng Williams in St Kitts from Barbados on 16 November 1997. They were also faxed subsequently on 21 November.

    The forms are:

    2.2 Field Surveys

    The shelters which are also schools on the list to be surveyed were:

    NEMA Number

    NEMA Shelter Category

    Name

    Location

    9

    main

    Verchilds High and Primary Schools

    Verchilds

    10

    main

    Newton Ground All Age School

    Newton Ground

    11

    main

    St Pauls Primary School

    St Pauls

    12

    secondary

    Tabernacle Primary School

    Tabernacle

    13

    main

    Molineux Primary School

    Molineux

    14

    secondary

    Cayon High School

    Cayon

    16

    main

    Basseterre High School

    Victoria Road & Park Range

    17

    main

    Basseterre Junior High School

    Taylors

    18

    main

    Fitzroy Bryant College

    Burdon Street

    19

    main

    Newtown Primary School

    Ponds Pasture

    20

    main

    St Peters Primary School

    St Peters

    Cromwell Williams proceeded with the field surveys in November and contact was made with him from time to time by Tony Gibbs and David Folkes. The programme was for the field work for the 11 shelters which were also school properties to be completed in time for Tony Gibbs' visit to St Kitts early in December.

    In accordance with the requirements for the work, completed survey forms were sent to Tony Gibbs in Barbados in advance of his St Kitts visit. This was done on 2 December 1997. (The photographs were not ready at that time.)

    Mr Bentley had undertaken to provide the photographs and these were delivered in duplicate (in a bound volume) to Tony Gibbs on his arrival in St Kitts on 6 December 1997.

    2.3 Field Reviews

    The first of these was undertaken by Tony Gibbs in the company of Cromwell Williams and David Folkes. The schools visited on 6 December were Basseterre Junior High School and Cayon School.

    Over the ensuing period, David Folkes accompanied Cromwell Williams on review visits to the remaining properties.  In addition, Eng Folkes made unaccompanied visits to some of the properties to gather supplementary information.

    2.4 Desk Studies

    To assist with the determination of vulnerability to hurricanes (and in accordance with the ToR) the software package WIND-RITE was utilised. WIND-RITE is a software system developed by the Wind Engineering Research Center at Texas Tech University, Lubbock, TX in conjunction with the Insurance Institute for Property Loss Reduction. This program is used to establish a relative grade for the wind resistance of buildings by assigning various vulnerability weights to: site environment, roof envelope, wall envelope, structural framing, and other secondary considerations.

    A relative grade between 1 and 10 is assigned to a building during the evaluation process. A relative grade of 1 indicates that the building is highly resistant to wind-induced damage (less damage), whereas a building which receives a relative grade of 10 is highly susceptible to wind-induced damage (extensive damage). For non-engineered construction, a score of five would be considered very satisfactory.

    To assist with the determination of vulnerability to earthquakes (and in accordance with the ToR) the methodology of Ahmed F Hassan [9] was used. This methodology relies mainly on readily accessible data for an existing building such as the dimensions and arrangement of its structural elements and the floor area. Masonry walls, concrete columns and steel columns are given progressively higher weightings in determining their contributions to seismic resistance. The end result is a comparative assessment of seismic vulnerability. A copy of Hassan’s paper is provided in Appendix II.


    3 RESULTS

    3.1 Vulnerability to Hurricanes

    3.1.1 General Observations

    It would not be unreasonable for the Government to require that its new, formally-designed, school buildings would have the capacity to be largely undamaged by a 50-year-return-period hurricane.

    The objective stated above requires simply the application of known technology by the school's architects and engineers to:

    The next requirement is for faithful attention to be paid during construction to the details incorporated in the drawings, schedules and technical specifications for the project. Supervision and inspection are central to success in this area of execution.

    The final requirement is for the property to be adequately maintained.

    The above precepts seem simple enough. Yet schools are often damaged and indeed sometimes destroyed by hurricane events no worse than the "design" storm. That design storm cannot be less than (and could reasonably be greater than) the "50-year" storm. These failures come about because of the failure of the systems (or the inadequacy of the systems) set up to order the construction industry and to maintain public property.

    3.1.2 Aspects of Vulnerability

    The experience of recent hurricanes has demonstrated that most failures occur to roofs, windows and external doors. In a very few cases there is damage (or collapse) of walls. In

    even fewer cases there is foundation failure. The experience in St Kitts provides confirmatory evidence of this pattern.

    Roofs:

    Windows (and other openings):

    External Doors:

    3.1.3 Summary of Results

    The table below summarises the conclusions of the survey with respect to wind vulnerability. A higher WIND-RITE Rating indicates a higher vulnerability to hurricane events.

    Property and Code Number

    Individual Building and Code Number

    Description of Property

    Vulnerable Areas

    WIND-RITE Rating

    Verchilds Primary & Secondary Schools
    SKN-VPS
    SKN-VPS-01 Single storey building offering approximately 2300 sq ft of sheltered floor area.
    Constructed in 1976.
    • Metal sheeting connections
    • Breeze block windows
    • Aluminium louvers

    7.63

    SKN-VPS-02a Single storey building offering approximately 2290 sq ft of sheltered floor area.
    Constructed in 1993.
    • Metal sheeting connections
    • Aluminium louvers
    7.58
    SKN-VPS-02b Single storey building offering approximately 960 sq ft of sheltered floor area.
    Constructed in 1976.
    • Metal sheeting connections
    • Aluminium louvers
    8.63
    SKN-VPS-03 Single storey building offering approximately 2300 sq ft of sheltered floor area.
    Constructed in 1993.
    • Metal sheeting connections
    • Breeze block windows
    7.58
    SKN-VPS-04 Single storey building offering approximately 2210 sq ft of sheltered floor area.
    Constructed in 1987.
    • Roof timber connections
    • Metal sheeting connections
    • Breeze block windows
    8.29
    SKN-VPS-05 Single storey building offering approximately 2200 sq ft of sheltered floor area.
    Constructed in 1976.
    • Metal sheeting connections
    • Breeze block windows
    8.63
    SKN-VPS-06 Single storey building offering approximately 2200 sq ft of sheltered floor area.
    Constructed in 1976.
    • Metal sheeting connections
    • Breeze block windows
    8.63
    SKN-VPS-07 Single storey building.
    Constructed in 1993.
    • Metal sheeting connections
    • Breeze block windows
    7.58
    SKN-VPS-08 Single storey building offering approximately 610 sq ft of sheltered floor area.
    Constructed in 1993.
    • Roof timber connections
    • Metal sheeting connections
    • Fixed timber louvers
    8.29
    SKN-VPS-09 Single storey building offering approximately 3540 sq ft of sheltered floor area.
    Constructed in 1996.
    • Roof timber connections
    • Metal sheeting connections
    • Breeze block windows
    8.29
    SKN-VPS-10 Single storey building offering approximately 590 sq ft of sheltered floor area.
    Constructed in 1976.
    • Metal sheeting connections
    • Fixed timber louvers
    8.63
    Newton Ground All Age School
    SKN-NGP
    SKN-NGP-01 Single storey building offering approximately 2370 sq ft of sheltered floor area.
    Constructed in 1958.
    • Metal sheeting connections
    • Breeze block windows
    8.63
    SKN-NGP-02 Single storey building offering approximately 430 sq ft of sheltered floor area.
    Constructed in 1958.
    • Roof timber connections
    • Metal sheeting connections
    • Breeze block windows
    8.42
    St Pauls Primary School
    SKN-SPA
    SKN-SPA-01 Single storey building offering approximately 2500sq ft of sheltered floor area.
    Constructed in 1982.
    • Roof timber connections
    • Metal sheeting connections
    • Breeze block windows
    8.86
    SKN-SPA-02 Single storey building offering approximately 2500sq ft of sheltered floor area.
    Constructed in 1982.
    • Roof timber connections
    • Metal sheeting connections
    • Breeze block windows
    • Aluminium louvers
    7.94
    SKN-SPA-03 Single storey building offering approximately 2500sq ft of sheltered floor area.
    Constructed in 1982.
    • Roof timber connections
    • Metal sheeting connections
    • Breeze block windows
    8.86
    Tabernacle Primary School
    SKN-TPS
    SKN-TPS-01/02 Single storey building offering approximately 4030 sq ft of sheltered floor area.
    Constructed in 1975.
    • Roof timber connections
    • Metal sheeting connections
    • Breeze block windows
    • Aluminium louvers
    9.36
    SKN-TPS-02 Single storey building offering approximately 4030 sq ft of sheltered floor area.
    Constructed in 1975.
    • Roof timber connections
    • Metal sheeting connections
    • Breeze block windows
    9.36
    Molineux Primary School
    SKN-MPS
    SKN-MPS-01 Single storey building offering approximately 220 sq ft of sheltered floor area.
    Constructed in 1946.
    • Roof timber connections
    • Metal sheeting connections
    • Glass windows
    8.86
    SKN-MPS-02 Single storey building offering approximately 1000 sq ft of sheltered floor area.
    Constructed in 1987.
    • Roof timber connections
    • Metal sheeting connections
    • Glass windows
    8.91
    Cayon High School
    SKN-CHS
    SKN-CHS-01 Two-storey building providing approximately 1680 sq-ft of sheltered floor area.
    Constructed in 1986
    • Metal sheeting connections
    • Aluminium louvers
    7.58
    SKN-CHS-02 Single storey building.
    Constructed in 1982.
    • Roof timber connections
    • Metal sheeting connections
    • Un-reinforced masonry walls
    • Aluminium louvers
    9.25
    SKN-CHS-03 Single storey building.
    Constructed in 1972.
    • Metal sheeting connections
    • Un-reinforced masonry walls
    • Aluminium louvers
    8.91
    SKN-CHS-04 Single storey building.
    Constructed in 1972.
    • Metal sheeting connections
    • Un-reinforced masonry walls
    • Aluminium louvers
    8.03
    SKN-CHS-05 Insufficient information
    • Insufficient information
    N/A
    SKN-CHS-06 Single storey building.
    Constructed in 1972.
    • Metal sheeting connections
    • Un-reinforced masonry walls
    • Aluminium louvers
    8.03
    SKN-CHS-07 Single storey building.
    Constructed in 1994.
    • Roof timber connections
    • Metal sheeting connections
    • Aluminium louvers
    8.37
    SKN-CHS-08 Single storey building.
    Constructed in 1972.
    • Metal sheeting connections
    • Un-reinforced masonry walls
    • Aluminium louvers
    8.03
    SKN-CHS-09 Single storey building.
    Constructed in 1972.
    • Metal sheeting connections
    • Un-reinforced masonry walls
    • Aluminium louvers
    8.73
    SKN-CHS-10 Single storey building.
    Constructed in 1972.
    • Metal sheeting connections
    • Un-reinforced masonry walls
    • Aluminium louvers
    8.73
    SKN-CHS-11 Two-storey building.
    Constructed in 1972.
    • Metal sheeting connections
    • Un-reinforced masonry walls
    • Aluminium louvers
    8.01
    SKN-CHS-12 Single storey building.
    Constructed in 1976.
    • Un-reinforced masonry walls
    • Aluminium louvers
    7.69
    Basseterre High School
    SKN-BHS
    SKN-BHS-01 Two-storey building offering approximately 2080 sq-ft of sheltered floor area.
    • Insufficient information
    N/A
    SKN-BHS-02 Single storey building offering approximately 420 sq-ft of sheltered floor area.
    • Insufficient information
    N/A
    SKN-BHS-03 Single storey building offering approximately 510 sq-ft of sheltered floor area.
    • Insufficient information
    N/A
    SKN-BHS-04 Single storey building offering approximately 840 sq-ft of sheltered floor area.
    • Insufficient information
    N/A
    Basseterre Junior High School
    SKN-BJH
    SKN-BJH-01 Two-storey building.
    Constructed in 1979.
    • Aluminium louvers
    7.69
    SKN-BJH-02 Two-storey building.
    Constructed in 1979.
    • Aluminium louvers
    7.69
    SKN-BJH-03 Two-storey building.
    Constructed in 1979.
    • Aluminium louvers
    8.69
    SKN-BJH-04 Two-storey building.
    Constructed in 1979.
    • Aluminium louvers
    8.69
    SKN-BJH-05 Two-storey building.
    Constructed in 1979.
    • Aluminium louvers
    8.69
    SKN-BJH-06 Two-storey building.
    Constructed in 1979.
    • Aluminium louvers
    7.69
    Fitzroy Bryant College
    SKN-CFB
    SKN-CFB-01 Insufficient information
    • Glass windows
    N/A
    Newtown Primary School
    SKN-NPS
    SKN-NPS-01 Single storey building offering approximately 660 sq ft of sheltered floor area.
    Constructed in 1966.
    • Breeze block windows
    8.82
    SKN-NPS-02 Single storey building offering approximately 1040 sq ft of sheltered floor area.
    Constructed in 1981.
    • Breeze block windows
    8.86
    SKN-NPS-03 Single storey building offering approximately 940 sq ft of sheltered floor area.
    Constructed in 1966.
    • Breeze block windows
    8.44
    St Peters Primary School
    SKN-SPE
    SKN-SPE-01 Single storey building offering approximately 1440 sq ft of sheltered floor area.
    Constructed in 1974.
    • Aluminium louvers
    8.65
    SKN-SPE-02 Single storey building offering approximately 510 sq ft of sheltered floor area.
    Constructed in 1974.
    • Aluminium louvers
    8.71

    N/A indicates that a WIND-RITE result was not obtained due to insufficient survey information.

    The WIND-RITE analysis results appear to indicate that the properties have an approximate equally high vulnerability to hurricanes. It should be noted that the WIND-RITE program will produce high vulnerabilities if the building has unprotected openings and light-weight sheeting. Since these vulnerable areas can be mitigated against relatively easily, it is not considered prudent to exclude a property from being considered as a shelter based on these results.

    3.2 Vulnerability to Torrential Rain

    3.2.1 General Observations

    Property becomes vulnerable to torrential rain either directly, if the rain penetrates the building envelope, or indirectly, through the resultant flooding events. Improperly sealed window and door openings or roof covering can result in the immediate ingress of water, while poorly sited buildings, and/or buildings with inadequate or improperly maintained drainage systems can result in the property being vulnerable to flooding.

    The not so immediate effect of flooding caused by torrential rains is the adverse effect it can have on the foundations of buildings.

    Coastal areas can be particularly vulnerable to flooding especially if high tides accompany heavy rains. In addition, the groundwater level is generally higher in coastal areas resulting in less absorption by the ground and an increased incidence of flooding.

    3.2.2 Summary of Results

    The table below summarises the conclusions of the survey with respect to torrential rain vulnerability.

    Property and Code Number

    Individual Building and Code Number

    Location of Property Vulnerable Areas
    Verchilds Primary & Secondary Schools
    SKN-VPS
    SKN-VPS-01
    • Relatively flat topography
    • Coastal location
    • Breeze block windows
    • Aluminium louvers
    SKN-VPS-02a
    • Relatively flat topography
    • Coastal location
    • Aluminium louvers
    SKN-VPS-02b
    • Relatively flat topography
    • Coastal location
    • Aluminium louvers
    SKN-VPS-03
    • Relatively flat topography
    • Coastal location
    • Breeze block windows
    SKN-VPS-04
    • Relatively flat topography
    • Coastal location
    • Breeze block windows
    SKN-VPS-05
    • Relatively flat topography
    • Coastal location
    • Breeze block windows
    SKN-VPS-06
    • Relatively flat topography
    • Coastal location
    • Breeze block windows
    SKN-VPS-07
    • Relatively flat topography
    • Coastal location
    • Breeze block windows
    SKN-VPS-08
    • Relatively flat topography
    • Coastal location
    • Fixed timber louvers
    SKN-VPS-09
    • Relatively flat topography
    • Coastal location
    • Breeze block windows
    SKN-VPS-10
    • Relatively flat topography
    • Coastal location
    • Fixed timber louvers
    Newton Ground All Age School
    SKN-NGP
    SKN-NGP-01
    • Relatively flat topography
    • Coastal location
    • Breeze block windows
    SKN-NGP-02
    • Relatively flat topography
    • Coastal location
    • Breeze block windows
    St Pauls Primary School
    SKN-SPA
    SKN-SPA-01
    • Relatively flat topography
    • Coastal location
    • Breeze block windows
    SKN-SPA-02
    • Relatively flat topography
    • Coastal location
    • Breeze block windows
    • Aluminium louvers
    SKN-SPA-03
    • Relatively flat topography
    • Coastal location
    • Breeze block windows
    Tabernacle Primary School
    SKN-TPS
    SKN-TPS-01
    • Relatively flat topography
    • Coastal location
    • Breeze block windows
    • Aluminium louvers
    SKN-TPS-02
    • Relatively flat topography
    • Coastal location
    • Breeze block windows
    Molineux Primary School
    SKN-MPS
    SKN-MPS-01
    • Relatively flat topography
    • Residential rural location
    • Glass windows
    SKN-MPS-02
    • Relatively flat topography
    • Residential rural location
    • Glass windows
    Cayon High School
    SKN-CHS
    SKN-CHS-01
    • Relatively flat topography
    • Residential rural location
    • Aluminium louvers
    SKN-CHS-02
    • Relatively flat topography
    • Coastal location
    • Aluminium louvers
    SKN-CHS-03
    • Relatively flat topography
    • Coastal location
    • Aluminium louvers
    SKN-CHS-04
    • Relatively flat topography
    • Coastal location
    • Aluminium louvers
    SKN-CHS-05
    • Relatively flat topography
    • Coastal location
    • None apparent
    SKN-CHS-06
    • Relatively flat topography
    • Coastal location
    • Aluminium louvers
    SKN-CHS-07
    • Relatively flat topography
    • Coastal location
    • Aluminium louvers
    SKN-CHS-08
    • Relatively flat topography
    • Coastal location
    • Aluminium louvers
    SKN-CHS-09
    • Relatively flat topography
    • Coastal location
    • Aluminium louvers
    SKN-CHS-10
    • Relatively flat topography
    • Coastal location
    • Aluminium louvers
    SKN-CHS-11
    • Relatively flat topography
    • Coastal location
    • Aluminium louvers
    SKN-CHS-12
    • Relatively flat topography
    • Coastal location
    • Aluminium louvers
    Basseterre High School
    SKN-BHS
    SKN-BHS-01
    • Insufficient information
    • Insufficient information
    SKN-BHS-02
    • Insufficient information
    • Insufficient information
    SKN-BHS-03
    • Insufficient information
    • Insufficient information
    SKN-BHS-04
    • Insufficient information
    • Insufficient information
    Basseterre Junior High School
    SKN-BJH
    SKN-BJH-01
    • Relatively flat topography
    • Urban location
    • Aluminium louvers
    SKN-BJH-02
    • Relatively flat topography
    • Urban location
    • Aluminium louvers
    SKN-BJH-03
    • Relatively flat topography
    • Urban location
    • Aluminium louvers
    SKN-BJH-04
    • Relatively flat topography
    • Urban location
    • Aluminium louvers
    SKN-BJH-05
    • Relatively flat topography
    • Urban location
    • Aluminium louvers
    SKN-BJH-06
    • Relatively flat topography
    • Urban location
    • Aluminium louvers
    Fitzroy Bryant College
    SKN-CFB
    SKN-CFB-01
    • Insufficient information
    • Glass windows
    Newtown Primary School
    SKN-NPS
    SKN-NPS-01
    • Relatively flat topography
    • Coastal location
    • Breeze block windows
    SKN-NPS-02
    • Relatively flat topography
    • Coastal location
    • Breeze block windows
    SKN-NPS-03
    • Relatively flat topography
    • Coastal location
    • Breeze block windows
    St Peters Primary School
    SKN-SPE
    SKN-SPE-01
    • Relatively flat topography
    • Rural location
    • Aluminium louvers
    SKN-SPE-02
    • Relatively flat topography
    • Rural location
    • Aluminium louvers

    3.3 Vulnerability to Earthquakes

    3.3.1 Multi-hazard Design

    When compared with dealing with a single hazard, designing against multiple hazards is more than doubly difficult, especially when those hazards are wind and earthquake. Some favourable features of wind-resistant design are unfavourable for earthquake-resistant design and vice versa, eg:

    Both hurricanes and earthquakes impose horizontal loads on buildings. Earthquakes also impose significant vertical loads on the overall building. The vertical loading derived from wind is usually significant on parts of a building as determined by aerodynamic considerations.

    However, there are many similarities in the effective design and construction of buildings to resist hurricanes and earthquakes:

    There must be a realisation that there is a real risk that "design" forces may be exceeded. This is particularly so in the case of earthquakes where the design force is deliberately determined to be less than that expected during the anticipated life of the building. This leads to a requirement for redundancy in the structure and for "toughness" - the ability to absorb overloads without collapse.

    3.3.2 Differences Between Designing Against Earthquakes and Hurricanes

    There is a basic difference in the performance expectations in the event of an earthquake as opposed to a hurricane. A building is expected to survive its "design hurricane" with virtually no damage. Even a catastrophic hurricane should only lead to repairable damage. On the other hand the "design earthquake" is expected to cause (hopefully repairable) damage, and a catastrophic earthquake is likely to lead to a situation where the building cannot be repaired and must be demolished. In such an event success is measured by the absence of deaths and serious injuries.

    3.3.3 Aspects of Vulnerability

    Designing schools to be safe during earthquakes is a complex process requiring the involvement of specialist structural engineers. In St Kitts, as in most parts of the Caribbean, the problem is compounded because of the absence of mandatory earthquake-resistant standards and the lack of a tradition of conscious engineering attention to this subject. Indeed there is no consensus that the hazard is sufficiently serious to warrant concerted action. Thus successes in the area of earthquake-resistant construction tend to be accidental. This comes about principally when the dominant design criterion overrides the demands of earthquake-resistant design.

    The main problem areas are summarised below.

    Structural vulnerability was noted mainly in two-storey construction, buildings with concrete roofs, and in masonry walls where the presence of reinforcement was moot. (Since concrete block walls often collapse during seismic shaking, all concrete block walls should be reinforced and braced by the adjacent structures.)

    Internal lighting fixtures and utility equipment were generally not fastened to structural elements securely enough to withstand large ground accelerations.

    Closets and heavy furniture were generally not fastened or strapped to the walls where these constituted a danger or contained valuable property.

    3.3.4 Summary of Results

    The table below summarises the conclusions of the survey with respect to earthquake vulnerability. A higher Seismic Relative Vulnerability Number indicates a lower vulnerability to seismic events.

    Property and Code Number

    Individual Building and Code Number

    Structural Members

    Vulnerable Areas

    Seismic Relative Vulnerability Number

    Verchilds Primary & Secondary Schools
    SKN-VPS

     

     

    SKN-VPS-01 Structural steel frame. 6" thick reinforced masonry walls, lightweight roof. Single storey building. Masonry walls 0.42
    SKN-VPS-02a Structural steel frame. 6" thick reinforced masonry walls, lightweight roof. Single storey building. Masonry walls 0.23
    SKN-VPS-02b Structural steel frame. 6" thick reinforced masonry walls, lightweight roof. Single storey building.   FM
    SKN-VPS-03 Structural steel frame. 6" thick reinforced masonry walls, lightweight roof. Single storey building. Masonry walls 0.44
    SKN-VPS-04 Structural steel frame. 6" thick reinforced masonry walls, lightweight roof. Single storey building.   2.06
    SKN-VPS-05 Structural steel frame. 6" thick reinforced masonry walls, lightweight roof. Single storey building.   3.73
    SKN-VPS-06 Structural steel frame. 6" thick reinforced masonry walls, lightweight roof. Single storey building.   3.73
    SKN-VPS-07 Structural steel frame. 6" thick reinforced masonry walls, lightweight roof. Single storey building.   2.03
    SKN-VPS-08 Structural steel frame. 6" thick reinforced masonry walls, lightweight roof. Single storey building.   3.14
    SKN-VPS-09 Structural steel frame. 6" thick reinforced masonry walls, lightweight roof. Single storey building. Masonry walls 0.39
    SKN-VPS-10 Structural steel frame. 6" thick reinforced masonry walls, lightweight roof. Single storey building.   2.87
    Newton Ground All Age School
    SKN-NGP
    SKN-NGP-01 RC frame, 6" thick reinforced masonry walls, lightweight roof. Single storey building.   2.15
    SKN-NGP-02 RC frame, 6" thick reinforced masonry walls, lightweight roof. Single storey building.   FM
    St Pauls Primary School
    SKN-SPA
    SKN-SPA-01 RC frame, reinforced masonry walls, lightweight roof. Single storey building. Masonry walls 0.28
    SKN-SPA-02 RC frame, reinforced masonry walls, lightweight roof. Single storey building. Masonry walls 0.39
    SKN-SPA-03 RC frame, reinforced masonry walls, lightweight roof. Single storey building. Masonry walls 0.43
    Tabernacle Primary School
    SKN-TPS
    SKN-TPS-01 RC frame, reinforced masonry walls, lightweight roof. Single storey building.   5.37
    SKN-TPS-02 RC frame, reinforced masonry walls, lightweight roof. Single storey building.   5.37
    Molineux Primary School
    SKN-MPS
    SKN-MPS-01 RC frame, 6" thick reinforced masonry walls, lightweight roof. Single storey building.   0.875
    SKN-MPS-02 Timber structure. Lightweight roof. Single storey.   FM
    Cayon High School
    SKN-CHS
    SKN-CHS-01 RC frame. Reinforced concrete walls, lightweight roof. Two storey building. First storey FM
    SKN-CHS-02 RC frame. Un-reinforced masonry walls, lightweight roof. Single storey building. Un-reinforced masonry walls FM
    SKN-CHS-03 Structural steel frame, masonry walls, lightweight roof. Single storey building. Un-reinforced masonry walls FM
    SKN-CHS-04 Structural steel frame, masonry walls, lightweight roof. Single storey building. Un-reinforced masonry walls FM
    SKN-CHS-05   Un-reinforced masonry walls FM
    SKN-CHS-06 Structural steel frame, masonry walls, lightweight roof. Single storey building. Un-reinforced masonry walls FM
    SKN-CHS-07 RC frame. Reinforced masonry walls, lightweight roof. Single storey building. Un-reinforced masonry walls FM
    SKN-CHS-08 Structural steel frame, masonry walls, lightweight roof. Single storey building. Un-reinforced masonry walls FM
    SKN-CHS-09 Structural steel frame, masonry walls, lightweight roof. Single storey building. Un-reinforced masonry walls FM
    SKN-CHS-10 Structural steel frame, masonry walls, lightweight roof. Single storey building. Un-reinforced masonry walls FM
    SKN-CHS-11 Structural steel frame, masonry walls, lightweight roof. Single storey building. Un-reinforced masonry walls FM
    SKN-CHS-12 Structural steel frame, masonry walls, lightweight roof. Single storey building. Un-reinforced masonry walls FM
    Basseterre High School
    SKN-BHS
    SKN-BHS-01 RC frame, masonry walls. Two-storey building. First storey FM
    SKN-BHS-02 RC frame, masonry walls. Single storey building.   FM
    SKN-BHS-03 RC frame, masonry walls. Single storey building.   FM
    SKN-BHS-04 RC frame, masonry walls. Single storey building.   FM
    Basseterre Junior High School
    SKN-BJH
    SKN-BJH-01 RC frame. Reinforced concrete walls, lightweight roof. Two storey building. First storey FM
    SKN-BJH-02 RC frame. Reinforced concrete walls, lightweight roof. Two storey building. First storey FM
    SKN-BJH-03 RC frame. Reinforced concrete walls, lightweight roof. Two storey building. First storey FM
    SKN-BJH-04 RC frame. Reinforced concrete walls, lightweight roof. Two storey building. First storey FM
    SKN-BJH-05 RC frame. Reinforced concrete walls, lightweight roof. Two storey building. First storey FM
    SKN-BJH-06 RC frame. Reinforced concrete walls, lightweight roof. Two storey building. First storey FM
    Fitzroy Bryant College
    SKN-CFB
    SKN-CFB-01     FM
    Newtown Primary School
    SKN-NPS
    SKN-NPS-01 Structural steel frame, masonry walls, lightweight roof. Single storey building.   FM
    SKN-NPS-02 RC frame. Reinforced concrete walls, lightweight roof. Single storey building.   FM
    SKN-NPS-03 RC frame. Reinforced masonry walls, lightweight roof. Single storey building.   FM
    St Peters Primary School
    SKN-SPE
    SKN-SPE-01 RC frame. Reinforced concrete walls, lightweight roof. Single storey building.   FM
    SKN-SPE-02 RC frame. Reinforced masonry walls, lightweight roof. Single storey building.   FM

    4 GENERAL ISSUES

    4.1 Impact of Hurricanes on Caribbean Schools

    Hurricanes David in 1979, Allen in 1980, Hugo in 1989 and Luis in 1995 caused significant damage to schools in Dominica, St. Lucia, Montserrat and Antigua respectively. The review of the damage to most of the schools showed that roof failure was the primary cause of problems, leading in some cases to complete collapse of the walls. Most of the roofs were made of wooden rafters or trusses with 26-gauge (or thinner) galvanised sheeting. Few roofs of aluminium sheeting survived. Some roofs remained partially intact but the damage to windows, doors and internal partitions was significant. Some wooden structures were completely destroyed, sometimes by falling trees and sometimes by being blown off their foundations.

    In general, therefore, the response of the school buildings to hurricane forces must be judged to have been poor. It is disturbing to note that the reconstruction of many of the schools which suffered from the recent hurricanes and the construction of some new schools have been based on the same design concepts which have led to the failures.

    4.2 Hazards versus Disasters

    Disasters are often seen as unpredictable, having to do with luck and part of the risks of everyday living. Surely we have progressed beyond the stage when superstition, mythology and fatalism were the public responses to natural hazards. Hurricanes are not natural disasters, they are natural events which sometimes lead to manmade disasters. In these days of widespread technological education, sophisticated research, reliable building materials, computer-based geographical information systems and satellite-assisted warning programmes, hurricanes in the Caribbean should not lead to disasters. The one exception to this would be vulnerable agricultural crops such as bananas.

    It is now evident that disasters due to natural hazards are largely preventable and soon the public will demand deliberate actions to protect communities against hazardous events.

    4.3 Codes and Standards

    The development and maintenance of building standards and codes is a continuing process in many countries. The mandate of national or regional professional and governmental institutions usually includes the development of building standards and the co-ordination of such activities among its various constituent members.

    To date the majority of countries (including St Kitts - Nevis) are without satisfactory, mandatory standards dealing adequately with any of the prevalent natural hazards.

    4.4 The Regulatory Environment

    Some government agencies adopt an ad hoc approach to standards based, principally, on the particular individuals involved in the specific projects. In most cases the administrators tacitly assume that their designers and builders would do what is right without being told. In other cases the administrators adopt the approach of not objecting to safe design and construction, provided that these attributes do not interfere with their other aims for the projects.

    Many government capital works projects are funded by international lending agencies. Typically there is a reluctance on the part of these agencies to impose structural design criteria on their projects. The funding agencies leave it up to the governments and the governments leave it up to their designers and builders. This laissez-faire approach leads to inconsistent performance, lack of reliability and, arguably, to higher overall life-cycle costs for the built environment.

    Building codes (incorporating appropriate standards) must be adopted immediately. Sufficient technical documentation exists. The fact that such documentation has deficiencies should not be an excuse for non-implementation. Codes and standards can be improved only through usage, which leads to inevitable revisions.

    The system of check consultants (bureaux de contrôle), routinely used in French territories, is proposed. Check consultants are independent of the design consultants. It is well recognised that quality assurance is more effective where checking is done independently of creating. The system mentioned above formalises the process.

    4.5 Public Awareness

    During the past 111 years a total of approximately 1000 tropical storms and hurricanes have been recorded over the North Atlantic area. Of these, about 50 percent were hurricanes, many in the general area of the Caribbean. With such a record, it is not surprising that everyone in this region accepts that hurricanes are a fact of life. However, the frequency of direct hits by hurricanes on any one territory is low. This has led to a considerable lack of consciousness amongst Caribbean people as to the dangerous risk to their own properties. Few believe that their island would be hit.

    In the post-Columbian history of St Kitts and Nevis there have been 80 recorded hurricane events which have affected these islands. Not all of these were direct hits by hurricane-force winds. In many cases the effects were by way of heavy seas and torrential rain. The most recent of these events were hurricanes Hugo (1989), Luis (1995) and Marilyn (1995). None of these three events produced more than minimum hurricane winds. The damage that can be expected from direct hits from such hurricanes is one or two orders of magnitude greater than what occurred in those two years. The success of school buildings during those hurricanes cannot be regarded as proof of adequacy.

    4.6 Vulnerability Surveys

    4.6.1 Qualitative Assessment

    This is the level of assessment being carried out in the present programme. This level of evaluation does not envisage exhaustive testing of materials in place nor sophisticated computation of stresses. It does involve a careful review of all readily available data (such as drawings), an inspection of the building without destructive testing and a non-mathematical review of the data.

    4.6.2 Analytical Evaluation

    Facilities whose performances are deemed to be doubtful when assessed qualitatively would be subjected to an analytical evaluation. This procedure would also be used as a second stage, prior to implementation of retrofitting, in cases deemed to be self-evidently inadequate by qualitative assessment. Since analytical evaluation is a time-consuming and expensive exercise it would be appropriate to carry it out only when the funds were available for implementing the possible actions indicated by such evaluation.

    It is envisaged that analytical evaluations will be undertaken for those schools selected for the CDB retrofit project.

    4.7 Disaster Mitigation after the Event

    In the aftermath of a disaster the focus is understandably on getting educational facilities to function again as soon as possible. Also, technical personnel and financial resources are spread very thin at such times. This combination of factors often leads to repairs being carried out in an expedient manner without adequate attention to safety issues. Indeed, post-disaster repairs often leave the buildings even more vulnerable than they were in their pre-disaster, inadequate states. There are examples of this in St Kitts.

    If such a scenario is to be avoided, very deliberate steps must be taken by the custodians of the educational facilities. Such actions would include:

    4.8 Maintenance as a Tool for Mitigation

    The physical condition of many Caribbean schools is poor. Windows and doors show lack of maintenance and repair. It is considered that a major effort should be taken to bring the condition of the buildings to the standard where a normal maintenance crew can be expected to deal with the routine maintenance requirements of the facility. It is considered, also, that the existing staff and maintenance budget are generally insufficient to provide for proper maintenance.

    It is recommended that for public buildings with the heavy use of a school, the annual maintenance budget should amount to about 4% of the contemporary capital cost of the building and equipment, assuming that the facilities are in good condition to start with. For schools, it is estimated that the replacement cost is about US$150,000 per classroom. (This figure includes amounts for common and administrative areas as well as infrastructure.) The maintenance allocation should therefore be no less than US$6,000 per classroom per year.

    The maintenance of a school, rather than being a one-time activity as is the construction of the school, is a continuous daily operation of the institution and is an important ingredient in the delivery of education.

    A good maintenance system is also a good disaster mitigation system, as the review of damage caused by recent hurricanes and floods has shown. To some extent the damage to buildings was due to lack of sustained maintenance of critical items. Also, a well operated system of maintenance for buildings and equipment has the effect of being a very effective disaster mitigation measure in terms of cost and facility usage. It ensures the most economic way to keep the building and equipment in the best of form for normal use, given the original design and materials. It is essential that a maintenance plan be included in disaster mitigation plans.

    It should be noted that the establishment of a secure and orderly system of archiving of construction drawings depicting the as-built condition of the final structure is an essential ingredient of the long-term maintenance schedule of any constructed facility. Because the archive will serve its purpose over the lifetime of the facility, the protection of its contents against the effects of time cannot be overlooked.


    5 HURRICANES LUIS AND MARILYN IN ST KITTS

    5.1 Damage and Repairs

    As a result of hurricanes Luis and Marilyn in 1995, the following general damage to the school buildings was reported:

    Most of the buildings have been subsequently repaired. The damage and repairs are described in the following table.

    Property and Code Number

    Individual Building and Code Number

    Description of Damage

    Repairs and Reconstruction

    Verchilds Primary & Secondary Schools
    SKN-VPS
    SKN-VPS-01 to 10
    • Unknown
    • Unknown
    Newton Ground All Age School
    SKN-NGP
    SKN-NGP-01 & 02
    • Unknown
    • Unknown
    St Pauls Primary School
    SKN-SPA
    SKN-SPA-01 to 03
    • Unknown
    • Unknown
    Tabernacle Primary School
    SKN-TPS
    SKN-TPS-01 & 02
    • Unknown
    • Unknown
    Molineux Primary School
    SKN-MPS
    SKN-MPS-01 & 02
    • Unknown
    • Unknown
    Cayon High School
    SKN-CHS
    SKN-CHS-01
    • Number of roof sheets blown off.
    • Roof replaced by the same standard as before the storm.
    SKN-CHS-02
    • Roof lost.
    • Roof replaced by the same standard as before the storm.
    SKN-CHS-03 to 12
    • Unknown
    • Unknown
    Basseterre High School
    SKN-BHS
    SKN-BHS-01
    • Roof sheeting lost.
    • All major items of repairs had been completed.
    SKN-BHS-02
    • Loss of small section of sheeting and raised sheet.
    • Smashed windows and doors.
    • Water damage due to number of leaks.
    • All major items of repairs had been completed.
    SKN-BHS-03
    • Roof lost.
    • Doors and windows damaged.
    • All major items of repairs had been completed.
    SKN-BHS-04
    • Unknown
    • Unknown
    Basseterre Junior High School
    SKN-BJH
    SKN-BJH-01
    • Loss of roof sheeting and purlins.
    • Roof gutters and down pipes blown off or damaged.
    • Essential repairs were completed.
    SKN-BJH-02
    • Loss of roof sheeting and purlins.
    • Roof gutters and down pipes blown off or damaged.
    • Essential repairs were completed.
    SKN-BJH-03
    • Loss of roof sheeting and purlins.
    • Roof gutters and down pipes blown off or damaged.
    • Essential repairs were completed.
    SKN-BJH-04
    • Loss of roof sheeting and purlins.
    • Roof gutters and down pipes blown off or damaged.
    • Essential repairs were completed.
    SKN-BJH-05
    • Loss of roof sheeting and purlins.
    • Roof gutters and down pipes blown off or damaged.
    • Essential repairs were completed.
    SKN-BJH-06
    • Loss of roof sheeting and purlins.
    • Roof gutters and down pipes blown off or damaged.
    • Essential repairs were completed.
    Fitzroy Bryant College
    SKN-CFB
    SKN-CFB-01
    • Unknown
    • Unknown
    Newtown Primary School
    SKN-NPS
    SKN-NPS-01 to 03
    • Unknown
    • Unknown
    St Peters Primary School
    SKN-SPE
    SKN-SPE-01
    • Entire roof , cladding and structure lost.
    • New structures were upgraded. Trusses and larger timber sizes used.
    • Straps and ties were incorporated in the reconstruction.
    SKN-SPE-02
    • Entire roof , cladding and structure lost.
    • New structures were upgraded. Trusses and larger timber sizes used.
    • Straps and ties were incorporated in the reconstruction.

    5.2 Recommendations

    The following recommendations are made with a view to reducing the vulnerability of the buildings surveyed to hurricanes, torrential rains, and earthquakes. The activities required are generally:

    1. Protect glass windows and doors with approved shutters.
    2. Stop the rainwater ingress through breeze blocks by installing shutters.
    3. Secure the timber shutters at the corners by installing bolts.
    4. Improve timber roof framing connections by installing approved hurricane straps and ties.
    5. Improve the roof sheeting connections by installing additional screws in vulnerable roof areas.
    6. Improve the water tightness of the aluminium louver windows.
    7. Strengthen un-reinforced masonry walls.
    8. Improve the drainage around the property.

    If these recommendations are carried out, then all of the properties surveyed can be used as shelters. The following table summarises the recommendations for each property.

    Property and Code Number

    Individual Building and Code Number

    Recommendation

    Verchilds Primary & Secondary Schools
    SKN-VPS
    SKN-VPS-01
    • Install additional screws in vulnerable roof areas.
    • Provide shutters to cover the breeze blocks.
    • Improve water tightness of aluminium louvers.
    SKN-VPS-02a
    • Install additional screws in vulnerable roof areas.
    • Improve water tightness of aluminium louvers.
    SKN-VPS-02b
    • Install additional screws in vulnerable roof areas.
    • Improve water tightness of aluminium louvers.
    SKN-VPS-03
    • Install additional screws in vulnerable roof areas.
    • Provide shutters to cover the breeze blocks.
    SKN-VPS-04
    • Improve timber roof framing connections.
    • Install additional screws in vulnerable roof areas.
    • Provide shutters to cover the breeze blocks.
    SKN-VPS-05
    • Install additional screws in vulnerable roof areas.
    • Provide shutters to cover the breeze blocks.
    SKN-VPS-06
    • Install additional screws in vulnerable roof areas.
    • Provide shutters to cover the breeze blocks.
    SKN-VPS-07
    • Install additional screws in vulnerable roof areas.
    • Provide shutters to cover the breeze blocks.
    SKN-VPS-08
    • Improve timber roof framing connections.
    • Install additional screws in vulnerable roof areas.
    • Provide shutters to cover the fixed timber louvers.
    SKN-VPS-09
    • Improve timber roof framing connections.
    • Install additional screws in vulnerable roof areas.
    • Provide shutters to cover the breeze blocks.
    SKN-VPS-10
    • Install additional screws in vulnerable roof areas.
    • Provide shutters to cover the fixed timber louvers.
    Newton Ground All Age School
    SKN-NGP
    SKN-NGP-01
    • Install additional screws in vulnerable roof areas.
    • Provide shutters to cover the breeze blocks.
    SKN-NGP-02
    • Improve timber roof framing connections.
    • Install additional screws in vulnerable roof areas.
    • Provide shutters to cover the breeze blocks.
    St Pauls Primary School
    SKN-SPA
    SKN-SPA-01
    • Improve timber roof framing connections.
    • Install additional screws in vulnerable roof areas.
    • Provide shutters to cover the breeze blocks.
    SKN-SPA-02
    • Improve timber roof framing connections.
    • Install additional screws in vulnerable roof areas.
    • Provide shutters to cover the breeze blocks.
    • Improve water tightness of aluminium louvers.
    SKN-SPA-03
    • Improve timber roof framing connections.
    • Install additional screws in vulnerable roof areas.
    • Provide shutters to cover the breeze blocks.
    Tabernacle Primary School
    SKN-TPS
    SKN-TPS-01
    • Improve timber roof framing connections.
    • Install additional screws in vulnerable roof areas.
    • Provide shutters to cover the breeze blocks.
    • Improve water tightness of aluminium louvers.
    SKN-TPS-02
    • Improve timber roof framing connections.
    • Install additional screws in vulnerable roof areas.
    • Provide shutters to cover the breeze blocks.
    Molineux Primary School
    SKN-MPS
    SKN-MPS-01
    • Improve timber roof framing connections.
    • Install additional screws in vulnerable roof areas.
    • Protect glass windows.
    SKN-MPS-02
    • Improve timber roof framing connections.
    • Install additional screws in vulnerable roof areas.
    • Protect glass windows.
    Cayon High School
    SKN-CHS
    SKN-CHS-01
    • Install additional screws in vulnerable roof areas.
    • Improve water tightness of aluminium louvers.
    SKN-CHS-02
    • Improve timber roof framing connections.
    • Install additional screws in vulnerable roof areas.
    • Strengthen un-reinforced masonry walls.
    • Improve water tightness of aluminium louvers.
    SKN-CHS-03
    • Install additional screws in vulnerable roof areas.
    • Strengthen un-reinforced masonry walls.
    • Improve water tightness of aluminium louvers.
    SKN-CHS-04
    • Install additional screws in vulnerable roof areas.
    • Strengthen un-reinforced masonry walls.
    • Improve water tightness of aluminium louvers.
    SKN-CHS-05
    • Insufficient information
    SKN-CHS-06
    • Install additional screws in vulnerable roof areas.
    • Strengthen un-reinforced masonry walls.
    • Improve water tightness of aluminium louvers.
    SKN-CHS-07
    • Install additional screws in vulnerable roof areas.
    • Strengthen un-reinforced masonry walls.
    • Improve water tightness of aluminium louvers.
    SKN-CHS-08
    • Install additional screws in vulnerable roof areas.
    • Strengthen un-reinforced masonry walls.
    • Improve water tightness of aluminium louvers.
    SKN-CHS-09
    • Install additional screws in vulnerable roof areas.
    • Strengthen un-reinforced masonry walls.
    • Improve water tightness of aluminium louvers.
    SKN-CHS-10
    • Install additional screws in vulnerable roof areas.
    • Strengthen un-reinforced masonry walls.
    • Improve water tightness of aluminium louvers.
    SKN-CHS-11
    • Install additional screws in vulnerable roof areas.
    • Strengthen un-reinforced masonry walls.
    • Improve water tightness of aluminium louvers.
    SKN-CHS-12
    • Install additional screws in vulnerable roof areas.
    • Strengthen un-reinforced masonry walls.
    • Improve water tightness of aluminium louvers.
    Basseterre High School
    SKN-BHS
    SKN-BHS-01
    • Insufficient information
    SKN-BHS-02
    • Insufficient information
    SKN-BHS-03
    • Insufficient information
    SKN-BHS-04
    • Insufficient information
    Basseterre Junior High School
    SKN-BJH
    SKN-BJH-01
    • Improve water tightness of aluminium louvers.
    SKN-BJH-02
    • Improve water tightness of aluminium louvers.
    SKN-BJH-03
    • Improve water tightness of aluminium louvers.
    SKN-BJH-04
    • Improve water tightness of aluminium louvers.
    SKN-BJH-05
    • Improve water tightness of aluminium louvers.
    SKN-BJH-06
    • Improve water tightness of aluminium louvers.
    Fitzroy Bryant College
    SKN-CFB
    SKN-CFB-01
    • Protect glass windows.
    Newtown Primary School
    SKN-NPS
    SKN-NPS-01
    • Provide shutters to cover the breeze blocks.
    SKN-NPS-02
    • Provide shutters to cover the breeze blocks.
    SKN-NPS-03
    • Provide shutters to cover the breeze blocks.
    St Peters Primary School
    SKN-SPE
    SKN-SPE-01
    • Improve water tightness of aluminium louvers.
    SKN-SPE-02
    • Improve water tightness of aluminium louvers.

    5.3 Classes of Vulnerability

    From the mitigating measures described in Section 5.2, several classes of vulnerability are identified. They are:

    1. Vulnerable roof
    2. Vulnerable walls
    3. Vulnerable dominant openings

    The following table identifies the vulnerable classes for each property.

    Property and Code Number

    Individual Building and Code Number

    Vulnerable Roof

    Vulnerable Walls

    Vulnerable Openings

    Verchilds Primary & Secondary School
    SKN-VPS

    SKN-VPS-01

    a

     

    a

    SKN-VPS-02a

    a

     

    a

    SKN-VPS-02b

    a

     

    a

    SKN-VPS-03

    a

     

    a

    SKN-VPS-04

    a

     

    a

    SKN-VPS-05

    a

     

    a

    SKN-VPS-06

    a

     

    a

    SKN-VPS-07

    a

     

    a

    SKN-VPS-08

    a

     

    a

    SKN-VPS-09

    a

     

    a

    SKN-VPS-10

    a

     

    a

    Newton Ground All Age School
    SKN-NGP

    SKN-NGP-01

    a

     

    a

    SKN-NGP-02

    a

     

    a

    St Pauls Primary School
    SKN-SPA

    SKN-SPA-01

    a

     

    a

    SKN-SPA-02

    a

     

    a

    SKN-SPA-03

    a

     

    a

    Tabernacle Primary School
    SKN-TPS

    SKN-TPS-01

    a

     

    a

    SKN-TPS-02

    a

     

    a

    Molineux Primary School
    SKN-MPS

    SKN-MPS-01

    a

     

    a

    SKN-MPS-02

    a

     

    a

    Cayon High School
    SKN-CHS

    SKN-CHS-01

         

    SKN-CHS-02

    a

    a

    a

    SKN-CHS-03

    a

    a

    a

    SKN-CHS-04

    a

    a

    a

    SKN-CHS-05

         

    SKN-CHS-06

    a

    a

    a

    SKN-CHS-07

    a

    a

    a

    SKN-CHS-08

    a

    a

    a

    SKN-CHS-09

    a

    a

    a

    SKN-CHS-10

    a

    a

    a

    SKN-CHS-11

    a

    a

    a

    SKN-CHS-12

    a

    a

    a

    Basseterre High School
    SKN-BHS

    SKN-BHS-01

         

    SKN-BHS-02

         

    SKN-BHS-03

         

    SKN-BHS-04

         
    Basseterre Junior High School
    SKN-BJH

    SKN-BJH-01

       

    a

    SKN-BJH-02

       

    a

    SKN-BJH-03

       

    a

    SKN-BJH-04

       

    a

    SKN-BJH-05

       

    a

    SKN-BJH-06

       

    a

    Fitzroy Bryant College
    SKN-CFB

    SKN-CFB-01

       

    a

    Newtown Primary School
    SKN-NPS

    SKN-NPS-01

       

    a

    SKN-NPS-02

       

    a

    SKN-NPS-03

       

    a

    St Peters Primary School
    SKN-SPE

    SKN-SPE-01

       

    a

    SKN-SPE-02

       

    a

    5.4 Further Work

    The intent of this report is to classify the surveyed properties with respect to their vulnerable areas, and hence retrofit needs. This has been done. The next step is to provide global cost estimates for performing the retrofit tasks. This will be done in a subsequent report.


    REFERENCES

    1. Caribbean Disaster Mitigation Project funded by the United States Agency for International Development (USAID) and managed by the OAS
    2. European Community Humanitarian Office
    3. Insurance Institute for Property Loss Reduction
    4. International Development Research Centre, Ottawa, Canada
    5. 1000 gals is approximately equal to the acceleration due to gravity
    6. This is part of the OECS Building Code project funded by the United Nations Development Programme (UNDP) through the United Nations Centre for Human Settlements (UNCHS) or Habitat.
    7. kPa = kilopascals
    8. metres per second
    9. Seismic Vulnerability Assessment of Low-Rise Buildings in Regions with Infrequent Earthquakes by Ahmed F Hassan and Mete A Sozen, ACI Structural Journal, January-February 1997, pages 31 et seq